CVE-2021-22681: Rockwell Multiple Products Insufficient Protected Credentials
Rockwell Multiple Products · listed in the CISA catalog of actively exploited vulnerabilities since 2026-03-05.
- CVSS v3.1 (CISA ADP)
- 9.8
- critical
- EPSS (exploit probability, 30 days)
- 64%
- higher than 99.2% of all CVEs
- Added to CISA KEV
- 2026-03-05
- US federal due date 2026-03-26
- Automatable (CISA SSVC)
- yes
- technical impact: total
CVE-2021-22681 explained
CVE-2021-22681 is an insufficiently protected credentials vulnerability in Rockwell Automation Studio 5000 Logix Designer and RSLogix 5000. These tools use a key to verify that they are communicating with Logix controllers, and an unauthenticated attacker could bypass this verification and authenticate with CompactLogix, ControlLogix, DriveLogix, GuardLogix and SoftLogix controllers. CISA lists it as known to be exploited.
Impact
An unauthenticated attacker with network access could bypass the verification mechanism and authenticate to affected Logix controllers. No user interaction is needed, and attack complexity is low. Confidentiality, integrity and availability impacts are all high. CISA rates the issue as automatable, meaning it can be exploited at scale, with total technical impact on the affected component. CISA's catalog of known exploited vulnerabilities includes it. Whether it has been used in ransomware campaigns is unknown.
Who is affected
The CVE record lists Rockwell Automation Studio 5000 Logix Designer versions 21 and later and RSLogix 5000 versions 16 through 20. It also lists 15 controller models, including CompactLogix 1768, 1769, 5370, 5380, 5480; ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; and SoftLogix 5800. The CVE record names no fixed version.
Written with AI from the data on this page and checked against it automatically.
Official description
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.
CISA required action: Apply mitigations per vendor instructions, follow applicable BOD 22-01 guidance for cloud services, or discontinue use of the product if mitigations are unavailable.
CISA notes
Affected and fixed versions
From the CVE record published by the vendor or CVE numbering authority.
- Rockwell Automation Studio 5000 Logix Designer, RSLogix 5000, Logix ControllersAffectedFixed in
- 15 listed models (Compact GuardLogix 5370 … 5730)
- RSLogix 5000 Versions 16 through 20
- Studio 5000 Logix Designer: Versions 21 and later
all 15 listed versions
- Compact GuardLogix 5370
- CompactLogix 1768
- ControlLogix 5550
- DriveLogix 5560
- GuardLogix 5570
- SoftLogix 5800
- 1769
- 1794-L34
- 5370
- 5380
- 5480
- 5560
- 5570
- 5580
- 5730
not stated
| Product | Affected | Fixed in |
|---|---|---|
| Rockwell Automation Studio 5000 Logix Designer, RSLogix 5000, Logix Controllers |
all 15 listed versions
| not stated |
How to fix it
- The CVE record names no fixed version – check the vendor advisory and CISA's required action for updates and mitigations.
- Vendor advisory: support.rockwellautomation.com/app/answers/answer_view/a_…
- CISA's deadline for US federal agencies: 2026-03-26 (passed) – a useful benchmark for everyone else, too.
What to do
- Apply the mitigations in Rockwell Automation's advisory for CVE-2021-22681.
- Keep Logix controllers and engineering workstations off the internet and isolate them on segmented control networks.
- Restrict network access to controllers to trusted engineering hosts only.
- Check controllers for unexpected logic changes, configuration changes or unusual connections.
- If mitigations cannot be applied, follow CISA's required action and discontinue use of the affected product.
The CVE record names no fixed version. Follow the Rockwell Automation advisory and apply its mitigations. CISA requires applying mitigations per vendor instructions, following BOD 22-01 guidance for cloud services where applicable, or discontinuing use if mitigations are unavailable. Until then, isolate controllers from untrusted networks and limit access to trusted engineering systems.
Written with AI from the data on this page and checked against it automatically.
CISA's assessment (SSVC)
- Exploitation
- Exploited in the wild
- Automatable
- Yes – attackers can automate it at scale
- Technical impact
- Total – full control of the component or total information disclosure
Weakness: CWE-522 Insufficiently Protected Credentials CWE-522
Questions about CVE-2021-22681
- Is CVE-2021-22681 being exploited?
- Yes. CISA added it to its Known Exploited Vulnerabilities catalog on 2026-03-05, with a US federal due date of 2026-03-26. Ransomware use is listed as unknown.
- Does an attacker need credentials?
- No. The description states that an unauthenticated attacker could bypass the verification mechanism and authenticate with affected Logix controllers over the network.
- Is there a patched version?
- The CVE record names no fixed version. Consult the Rockwell Automation advisory for mitigations and follow CISA's required action.
Written with AI from the data on this page and checked against it automatically.
References
Data: CISA Known Exploited Vulnerabilities (public domain) · CVE Program records incl. CISA ADP enrichment · OSV.dev (CC BY 4.0) incl. Ubuntu and Debian security data · FIRST EPSS · endoflife.date. Updated automatically – facts last changed 2026-11-21. Always confirm with the vendor's or distribution's advisory before patching.